Control & networks

“ASi-5 and ASi-5 Safety are established in the market”

Text Thomas Rönitzsch, Bihl+WiedemannImage Bihl+Wiedemann

Josef Alaaddin, adjunct-teamleider technische support bij Bihl+Wiedemann.
Josef Alaaddin, adjunct-teamleider technische support bij Bihl+Wiedemann.

Easy installation, robust technology and low machine costs: AS-Interface has been one of the most efficient solutions for the field level for years. With ASi-5, the technology has taken a major step forward, enabling significantly higher data rates, shorter cycle times and easy integration of modern devices such as IO-Link sensors and actuators. In an interview, Josef Alaaddin, deputy team leader of technical support at Bihl+Wiedemann, explains why ASi-5 is already successful in numerous applications and the opportunities it offers for future automation solutions.

How has ASi-5 developed from Bihl+Wiedemann’s perspective?

“ASi-5 and ASi-5 Safety are now well established in the market. This is reflected in the more than 250,000 ASi-5 devices from us and other manufacturers that have already been installed in machines and systems. The technology is compelling both in standalone ASi-5 applications and in combination with ASi-3. Demand, particularly from warehouse and materials handling technology, packaging automation and process engineering, remains high. This is because ASi-5 can avoid or replace complex Ethernet solutions in many applications. And since ASi-5 is undoubtedly a success story for us, we are also currently developing an ASi-5 repeater, which will allow the maximum cable length, originally 200 metres, to be extended considerably in the future.”

Cable length is one factor, what advantages does ASi-5 offer for power distribution in the field?

“ASi-5, as a fieldbus for the lower level of automation, makes power distribution, an essential part of the technology, highly efficient and flexible. Power and data are carried by the familiar yellow profile cable with a cross-section of 1.5 mm², which is suitable for currents of up to 8 A. For higher power requirements, such as those of drives or valves, a second black profile cable can be used, with a cross-section of 2.5 mm² and a current rating of up to 20 A. Passive safety up to SIL3/PLe can also be implemented via the black cable. Installation using piercing technology, without connectors or additional modules, not only saves on wiring, material costs and installation time, but also makes the installation more streamlined and easier to follow than conventional fieldbuses or point-to-point connections. An ASi-5 string can power up to 62 nodes, allowing power distribution to be adjusted incrementally without additional cabling.”

Connecting sensors and actuators via ASi-5 modules with integrated IO-Link master ports and self-configuring ASi-5 I/O modules from Bihl+Wiedemann.

What do ASi-5’s additional capabilities mean for configuring ASi networks?

“Networks with ASi-5 components can be configured using an addressing device and the master, just as with ASi-3. The complexity of the configuration depends largely on the complexity of the desired automation solution. To provide our customers with the best possible support, we offer software suites that can significantly simplify and speed up configuration. These make it easy to configure IO-Link devices or set up frequency inverters. Parameters can be copied from one module to another, and from one project to another. Users can implement their projects directly from the integrated hardware catalogue using drag and drop, and test them on screen. We focus not only on machine builders but also on their customers, the system operators, so they can make optimal use of the machines.”

“It is important that they know and understand our products and solutions well. That is why at Bihl+Wiedemann we support users not only with technical assistance when they need it, but also provide information materials and training from the outset. These include our installation recommendations, best practices and troubleshooting guide, as well as a wide range of instructional videos on various topics on our website, and, more recently, our Bihl+Wiedemann Academy.”

Why does an installation with ASi-5 gateways offer cybersecurity advantages compared with other Ethernet-

based solutions?

“With ASi-5, the gateway with OPC UA forms the link between TCP/IP and the ASi installation. This also physically separates the Ethernet-based interfaces from the field level via ASi. This communication split prevents the ASi network from becoming a platform for cyberattacks. By using an ASi-5 module with an integrated IO-Link master instead of an IO-Link master with an integrated Ethernet interface, security vulnerabilities can be nipped in the bud. If there is one combination that is cybersecure, it is certainly ASi-5 with IO-Link. ASi-5 effectively acts as a protective shield, allowing IO-Link to operate without external threats.”

Een zakelijke vraag aan Bihl+Wiedemann GmbH? Get in touch

Companies in this story

Keep following this

Get an email when a new story is published. No account needed.