‘Measurement is knowledge’ becomes ‘measurement is management’

An in-depth look at instrumentation, diagnostics and control
Measurement and control technology has long been part of the wider plant ecosystem. The quality of an individual flowmeter or temperature sensor remains important, but true performance only emerges when the measurement chain, communications, diagnostics and control strategy are viewed as a single system.
At a time of tight margins and more stringent compliance requirements, the conversation is shifting from ‘how accurate is my measurement?’ to ‘how robust is my measurement, and what impact does it have on my process, energy use and downtime?’

Uncertainty is a design parameter
In practice, the difference between a ‘good’ and a ‘reliable’ measurement often comes down to installation, operating conditions, drift and maintenance, not the datasheet. Standards for flow measurement such as ISO 5167-1:2022 explicitly emphasise installation requirements and the determination of measurement uncertainty for differential-pressure flowmeters (orifice, nozzle, Venturi). For engineers, this is a useful reminder: if measurement uncertainty is not compatible with process objectives (quality, efficiency measurement, mass balance), then ‘more PID tuning’ is rarely the answer. Instead, the measurement strategy (location, conditioning, straight runs, impulse lines, validation) needs to be reviewed.


Diagnostics must be consistent and action-oriented
The rise of smart transmitters, positioners and analysers has had one side effect: an abundance of device-specific error codes. NAMUR NE107 addresses this by standardising diagnostics into four status categories (Failure, Function Check, Out of Specification, Maintenance Request). NAMUR recently revised NE107 (2025), further reinforcing the importance of consistent status messages and maintenance workflows.
This is not just ‘pretty HMI iconography’. It makes it possible to set up alarms and maintenance workflows that remain scalable, especially in plants with mixed brands. NE107 is also increasingly appearing in practical device applications, such as valve positioners that explicitly classify their condition messages according to NE107.
From 4-20 mA to Ethernet, right into Zone 0
Where measurement and control technology traditionally relied on 4-20 mA and fieldbuses, the landscape is shifting towards Ethernet in the field. Ethernet-APL is positioning itself as a robust, two-wire, loop-powered Ethernet physical layer based on 10BASE-T1L, designed for the harsh conditions (including hazardous areas) of process plants. Crucially, Ethernet-APL is increasingly moving beyond the pilot phase, with devices, field switches and ecosystem support becoming more widely available.
The promise is compelling: a single, consistent network concept that simplifies engineering, commissioning and troubleshooting while bringing more diagnostics ‘out of the device’. But implementation requires discipline: segmentation, asset management and agreements on data models/semantic layers suddenly become just as important as cable selection. The same shift is also evident in discrete environments, with more Ethernet reaching I/O, more diagnostics and greater data consistency.
Alongside wired Ethernet, wireless remains relevant, particularly where installation is costly or technically difficult. WirelessHART (IEC 62591:2016) is often described as a self-organising network that can handle obstacles in the process environment and securely transmit both process and device information. The best choice is rarely ideological (‘wired is better’): it comes down to range, latency, maintainability and, above all, which measurements are critical for closed-loop control and which are for monitoring/diagnostics.
Data must remain usable
The next step in measurement and control technology is not yet another protocol, but interoperable use of data. The OPC Foundation has published the OPC UA Field eXchange (UAFX) specifications, designed to exchange process and configuration data between automation components using OPC UA Client/Server and PubSub. UAFX consists of several parts (including Parts 80-83) that define Field eXchange and engineering/exchange in practical terms. Its relevance for instrumentation and automation teams is clear: less vendor lock-in for device integration and a greater chance of making diagnostics, configuration and process values available consistently, provided suppliers and users adopt it consistently.
PID remains the workhorse
Despite all the buzzwords, PID remains the foundation. The difference comes from systematically monitoring controller performance. ISA, for example, publishes technical guidance on PID algorithms, implementations and performance metrics (ISA-TR5.9). In practice, ‘loop quality’ translates into fewer oscillations, less wasted energy and less wear on final control elements. Tools and methods for control loop performance monitoring (CPM) are therefore increasingly used to systematically detect poor tuning, valve stiction, sensor noise or inappropriate filter settings. Reviews and studies show how CPM/diagnostics is becoming a discipline in its own right within process optimisation.
Especially valuable where constraints cost money
Where processes are tightly coupled and operate close to their limits (capacity, emissions, product quality), Model Predictive Control (MPC) quickly comes into play. Vendor literature often sums up the benefit as: tighter control against constraints, with lower energy and raw material costs. Academic perspectives also emphasise that the future of process control is moving towards greater scale, more diagnostics, and both model-based and data-driven techniques. But implementation depends on data quality and organisational integration. In short, MPC is not a ‘magic controller’, but a project that brings together measurement quality, model maintenance and process knowledge.
SIS is not an ‘extra alarm’
In many plants, basic process control and safety are blurred in discussions about instrumentation. It is important, however, to keep the distinction clear: IEC 61511-1:2016 sets out requirements for the specification, design, installation, operation and maintenance of Safety Instrumented Systems (SIS) in the process industry, so that they can reliably achieve or maintain a safe state. IEC 61511-1 (2016, including amendments) remains the key reference; in 2025, the IEC also published an updated series compilation of the 61511 documents. For measurement and control teams, this means that every ‘smart’ optimisation (additional measurements, different ranges, filtering, software-based plausibility checks) must be assessed in the context of the safety lifecycle, particularly when a single transmitter is used for both control and safety-instrumented functions.
No digitalisation without a metrological foundation
Finally, the more digital you become, the more painful drift can be. ISO points out that ISO/IEC 17025 is the reference framework for competent testing and calibration laboratories and reliable results. This matters to industry because traceability and uncertainty are not just QA tick-boxes: they determine whether you can trust your trends, mass balances or energy KPIs at all.